D-7 Hose and Hose Testing

Maintenance Manual

Date Revised: 08/18/2025

Last Modified: 09/04/2025 13:49

Export D-7 to PDF
Export -Entire D Manual- to PDF


Definitions

Note: The terms Supply Line and Attack Line Hose can be used differently in operational usage, as opposed to the NFPA definitions relating to design, design verification, and testing of new fire hose.

To clarify language usage:
Supply Hose and Attack Hose are designators that the NFPA assigned in order to categorize fire hose by pressure. Per the NFPA designations, Supply hose is used at or below 185 psi; Attack hose is used at pressures above 185 psi.

These titles are confusing to many fire departments, as in operational usage, you can attack with NFPA defined supply hose and supply with NFPA defined attack hose.


Double Jacketed Hose Types


Single Jacketed Hose Types



ANNUAL HOSE TEST

All fire hose assigned to fire companies is to be tested under the direction of the Battalion Chiefs. The annual testing of hose shall be completed during the month of May.

If hose fails physical inspection, it shall be removed from service and sent to the Maintenance Bureau.

It must be recognized that development of test pressures as high as 250 psi, used for service testing, introduces a serious accident potential. It is imperative that all members maintain a high level of situational awareness, and that all procedures are strictly followed.


Hose Testing Procedures


Retesting of Hose That Has Been Repaired

All hose that has been repaired shall be tested ASAP before the hose is put back in service and the results recorded. The Maintenance Bureau does not have the facilities or the manpower to test all hose that is repaired. It is, therefore, the station Captain's responsibility to see that this is completed and recorded on the previously mentioned inventory form 300-1 through the station dashboard 300-1.

Testing shall be completed by June 1st each year.



See Also: