SCBA, OXYGEN or SCUBA cylinders carried on the air wagons or on other apparatus should be visually inspected daily, using the 0700 Hour Check procedure, detailed later in this procedure. Certain problems or conditions, as noted in the 0700 check, would be cause to place a suspect cylinder out of service. Faulty equipment should be depressurized and sent to the Maintenance Bureau with SCBA Equipment Repair Form 300-16 for SCBA equipment or Repair Form 300-15 for OXYGEN and SCUBA cylinders as found on your station dashboard, within the TFRDweb website LINK
WARNING: If a high pressure cylinder is known to have been subjected to any unusual treatment, accident, or condition, it should be immediately placed out of service, depressurized and sent to the Maintenance Bureau.
Steel, aluminum and gray carbon fiber cylinders are tested every five (5) years. For air cylinders, this information should be on a label attached to the body of the cylinder. For oxygen and SCUBA cylinders, this information is stamped near the neck of the cylinder.
COMPRESSED GAS CYLINDER - SERVICE LIFE AND HYDROSTATIC TEST INTERVAL | |||
---|---|---|---|
CONSTRUCTION | TYPE | HYDRO-TEST EVERY | SERVICE LIFE |
STEEL | SCUBA, OXYGEN, ETC. | 5 YEARS | INDEFINITE* |
ALUMINUM | SCBA, SCUBA, OXYGEN, ETC. | 5 YEARS | INDEFINITE* |
CARBON FIBER COMPOSITE | SCBA GRAY | 5 YEARS | 15 YEARS |
* INDEFINITE AS LONG AS CYLINDER PASSES VISUAL INSPECTION AND HYDROSTATIC TESTING AT PRESCRIBED INTERVALS
NOTE: TFRD compressors are rated at 5000-6000 psi. ALL compressors shall be regulated to a maximum of 4500 psi output for filling SCBA cylinders.
Only Water Rescue Team members are authorized to fill S.C.U.B.A. cylinders.
Drain the condensate reservoir from the compressor weekly on tool day.
SCBA equipment must pass the tests listed below before use. If the equipment fails to meet any of the tests, the condition must be corrected before using the equipment. Observed deficit in the function of any component of the SCBA equipment will necessitate that component's removal from service. Faulty equipment should be sent to the Fire Maintenance Bureau with a SCBA Equipment Repair form 300-16. Spare harnesses are available on the air wagons or through the Fire Maintenance Bureau.
Inspect cylinders before use, and check for problems or conditions detailed as follows. If any are present, drain air and send to Maintenance Bureau. DO NOT REFILL.
Check for:
If a cylinder is known to have been subjected to any unusual treatment, accident, or condition, it should be immediately placed out of service, depressurized and sent to the Maintenance Bureau.
Observe the operation of the HUD device (Heads-Up Display) in the following steps:
The HUD has lights on the unit that indicate different functions and measurements. The following is a description of each:
RIGHT SIDE LED’s | |
---|---|
4 Green LED’s | Air cylinder tank has 75-100% |
3 Green LED’s | Air cylinder tank has 50-74% |
2 Yellow LED’s | Air cylinder tank has 34-49% |
1 Red LED | Air cylinder tank has 0-33% |
LEFT SIDE LED’s | |
Red for the following:![]() | •Primary Thermal Alarm - Flashing •PASS Pre-Alarm - Flashing •PASS Full Alarm - Solid •PASS Manual Activation - Solid •Electronics Failure - Flashing |
Blue flashing for the following:![]() | •Potential Thermal Alarm |
Yellow flashing for the following:![]() | •Low Battery Warning Condition |
Check the harness pressure gauge and, if necessary, release any pressure trapped in the system by opening the bypass knob. Remove the quick connect coupling from the air-cylinder. Squeeze both button’s and lift to unlock the clamp down latch, then slide the cylinder out.
Air cylinders should be recharged as soon as possible.
Cylinders should be stored completely filled only.
See Also: