| + | =====C-1 Acetylene Fires===== | ||
| + | ===Emergency Manual=== | ||
| + | ==Date Revised: 02/ | ||
| + | < | ||
| + | |||
| + | [[https:// | ||
| + | [[https:// | ||
| + | |||
| + | ---- | ||
| + | |||
| + | Policy/ | ||
| + | |||
| + | **1. Cylinder Fires** \\ \\ | ||
| + | - If the flame is around the valve, the regulator, or the threaded pressure plug, the flame can be wiped out with a wet rag or smothered with putty. | ||
| + | - Fire burning from a blown pressure plug will subside in a few minutes as refrigeration of the acetone (in which the acetylene is dissolved) takes place. \\ \\ | ||
| + | - Fire personnel shall protect exposed cylinders with fog streams. \\ \\ | ||
| + | - When the flame from the involved cylinder is approximately one foot high, it can be extinguished with a dry chemical extinguisher by applying the agent at the base of the flame and in the same direction as the escaping gas. \\ \\ | ||
| + | - When extinguishment is complete, fire personnel shall move the involved cylinder outdoors, where it will be less of a hazard. \\ \\ | ||
| + | **2. Fire Inside a Cylinder** | ||
| + | |||
| + | On rare occasions, un-observable flames will recede into the cylinder producing a hissing noise, and causing paint to burn off the cylinder. This is an extremely dangerous condition. \\ \\ | ||
| + | |||
| + | - Fire personnel witnessing this condition shall cool the cylinder with a narrow fog stream. \\ \\ | ||
| + | - Fire personnel shall secure nozzles in position to envelope the cylinder in spray and withdraw to a safe location until the burning process is complete. \\ \\ | ||
| + | - If, upon arrival, a loud hissing or frying noise is heard and the cylinder is cherry red, swelling, or bulging, crews shall evacuate the area and stay behind a substantial barricade while directing streams on the cylinder. An explosion producing fragmentation of the cylinder is likely. | ||
| + | |||
| + | \\ | ||
| + | ---- | ||
| + | See Also: | ||
| + | ---- | ||
| + | |||
| + | <- c_manual:c0 ^ c_manual: | ||